Normative reference

Oil resistance

VDE 0472 Part. 803/B
IRM 902 – ASTM n. 2
HD 505.2.1 Part. 10
UL 1581 Cl. 43 (only 60°C)
IEC 60811-2-1

Flame resistance

IEC 60332-1
EN 50265-2-1
UL 1581
CSA FT1
VDE 0472 Part. 804 B

UL-CSA standard

UL 1581
UL 758
CSA C.22 n. 210.2

 

Family Code

ORSH19

Share datasheet

Description

Multiconductor cables for motor control, with external earth to shield, with oil resistant jacket, UL-CSA approved

Application

Motor and servomotor control, suitable for reducing radio frequency noise to a minimum Restricted movements

Technical data

Minimum bending radius

15 x cable diameter

Conductor

Flexible bare copper according to:
VDE 0295 Class 5 col.3
UL 1581 Tab. 20.1

Insulation

Polypropylene – UL Style 80°C 1000 V

Colour code

Black with white numbers

Shield

Tinned copper wire braid O.C. ≥ 85% ± 5%
+ transparent polyester

Earth conductor

Yellow/green

Sheath

PVC
colour: grey Ral 7001
UL Style CSA 80°C 1000 V O.R.

Service temperature

-10°C +80°C for static application

Nominal voltage

1000 V

Testing voltage

4000 V for 5 minutes

Insulation resistance

≥ 200 MΩ x km at 20°C

 

Item Numbers

Codice articoloAWG/MCMFormazione AWG/KcmilsFormazione CEFormazione n° × tipo di fibraRiferimento OEMFormazione (n° × mmq)ColoreDiametro (mm)Cu (kg/km)Tiro
ORSH1901(3x1.5)+1.5T11.385
ORSH1902(3x2.5)+2.5T13.0130
ORSH1903(3x4)+4T15.0200
ORSH1904(3x6)+6T17.0280
ORSH1905(3x10)+10T20.5452
ORSH1906(3x16)+16T25.5746
ORSH1907(3x25)+25T31.01120
ORSH1908(3x35)+35T38.01440

T = yellow/green